Specifications CFW700

Power Supply

Voltage

Single Phase or Three Phase

200-240V (+10%, -15%)

Three phase

380-480V (+10%, -15%)

Frequency

50 / 60Hz +/- 2Hz

Displacement Power Factor (Cos)

Greater than 0.98

Enclosure

Degree of Protection

NEMA 1

Control

Control Modes

Volts per Hertz (Scalar)

Voltage Vector (VVW)

Sensorless Vector

Vector with encoder

Power Output

Sinusoidal PWM  (Space Vector Modulation)

IGBT Transistors

Switching Frequency

1.25, 2.0, 2.5, 5.0 or 10.0 kHz

Frequency Range

0-300 Hz in Scalar Mode; 120 Hz in Vector Mode

Overload Capacity

CT = Constant Torque, 150% overload / 60 sec.

VT = Variable Torque (Quadratic Load), 110% overload / 60 sec.

Control Inputs

8 programmable isolated digital inputs, 24Vdc logic

2 isolated programmable differential analog inputs 11 bit; programmable for current or voltage (0-10V, 4-20mA or 0-20mA)

Motor thermistor - PTC/PT100/KTY84

Incremental encoder input – 5 to 12V

Control Outputs

1 programmable relay output; NO/NC (Form C); 240Vac, 30Vdc / 0.75 A

4 programmable isolated open collector digital outputs; 24Vdc, 80mA max.

2 non-isolated programmable analog outputs 10 bit; programmable for current or voltage (0-10V, 4-20mA or 0-20mA)

Communication

Serial

Optional RS-232 serial interface, RS-485 with external RS-232/485 converter

Field Bus

Isolated RS-485 / Modbus RTU (standard)

CAN interface module (CANopen/DeviceNet)

Profibus DP interface module

Safety

Protections

Motor over current

DC link over voltage

Motor overload

DC link under voltage

Output phase-to-phase short circuit

Drive  over temperature

Output phase-to-ground short circuit

External fault

Programming error

 

Ambient

Temperature

14 - 122°F (50°C), up to 140°F (60°C) with 2% / 1.8°F (1°C) output current derating

Humidity

5-90% Non Condensing

Altitude

0-3300 ft (1000m), up to 13,200 ft (4000m) with 1% output current derating per 330ft (100m) above 3300 ft (1000m).

Regulatory / Safety Conformance

IEC 60146

Semiconductor convertors

UL 508 C

Power Conversion Equipment

UL 840

Insulation coordination including clearances and creepage distances for electrical equipment.

UL 94

Plenum Rated - Meets UL94 Standard for Tests for Flammability

EN 50178

Electronic equipment for use in power installations

EN 61800-2

General requirements adjustable speed electrical power drive systems

EN 61800-3

EMC product standard including specific test methods adjustable speed electrical power drive systems

EN 61800-5-1

Safety requirements adjustable speed electrical power drive systems

EN 60204-1

Safety of machinery. Electrical equipment of machines. Part 1: General requirements.

RoHS and WEEE Guidelines

 

Approvals

UL, cUL, CE, C-Tick, GOST, IRAM

Special Functions

Linear and “S” ramp accel and decel, local/remote control, FWD/REV selection, DC braking, manual and auto torque boost, motor slip compensation, electronic pot, two skip frequencies, max. and min. adjustable frequency limits, adjustable output current, PID Controller

Keypad

Backlit LCD display with 9 operator keys, remote mounting option available

Readouts for: output frequency (Hz), output current (A), output voltage (V), motor torque (%) in vector mode, DC bus voltage (V), value proportional to frequency (Ex.: RPM), heatsink temperature, fault and status messages