Specifications CFW10
Power Supply |
Voltage |
Single phase |
110-127 Vac (+10%, -15%) |
Single phase |
200-240 Vac (+10%, -15%) |
||
Frequency |
50 / 60Hz +/- 2Hz |
||
Displacement Power Factor (Cos) |
Greater than 0.98 |
||
Enclosure |
Degree of Protection |
IP20 |
|
Control |
Control Mode |
Linear or Quadratic V/Hz |
|
Power Output |
IGBT Transistors |
||
Sinusoidal PWM (Space Vector Modulation) |
|||
Switching Frequency |
2.5, 5, 10 or 15kHz |
||
Frequency Range |
0-300 Hz |
||
Overload Capacity |
150% for 60 seconds, repeatable every 10 min. |
||
Control Inputs |
4 programmable isolated digital inputs |
||
1 programmable differential analog input: 0-10V, 0-20mA or 4-20mA |
|||
Control Outputs |
1 programmable relay output: Form C contacts rated 250V / 0.5A |
||
Safety |
Protections |
Motor over current |
DC link over voltage |
Motor overload |
DC link under voltage |
||
Output phase-to-phase short circuit |
Drive over temperature |
||
Output phase-to-ground short circuit |
External fault |
||
Programming error |
|
||
Ambient |
Temperature |
32°F (0°C), up to 122°F (50°C) without output current derating |
|
Humidity |
5-90% Non Condensing |
||
Altitude |
0-3300 ft (1000m), up to 13,200 ft (4000m) with 1% / 330ft (100m) output current derating |
||
Regulatory Conformance |
EMC Directive 89 / 336 / EEC |
Electromagnetic compatibility, Industrial Environment EMC Emission and Immunity |
|
ENC61800-3 for the FA version - optional |
|||
LVD 73/23/EEC |
Low Voltage Directive |
||
UL 508 C |
Power Conversion Equipment |
||
Special Functions |
Linear and “S” ramp accel and decel, local/remote control, FWD/REV selection, DC braking, manual and auto torque boost, mo- tor slip compensation, electronic pot, two skip frequencies, maximum and minimum adjustable frequency limits, adjustable out- put current limit, 8 present speeds and JOG, PID Controller |
||
Keypad |
3 digit display, 2 indication LEDs and 4 keys |
||
Readouts for: output freqency (Hz), output current (A), output voltage (V), value proportional to frequency (Ex: RPM), heatsink temperature, fault and status messages. |
|||
Mounting |
Surface mounting with screws |